Air Handling Design Info
Chart 1
CFM requirements for
diameter at specified velocity. |
| Diameter |
3500 FPM |
4000 FPM |
4500 FPM |
| 3" |
170 |
195 |
220 |
| 4" |
300 |
350 |
390 |
| 5" |
475 |
550 |
610 |
| 6" |
700 |
785 |
880 |
| 7" |
950 |
1100 |
1200 |
| 8" |
1200 |
1400 |
1570 |
| 9" |
1550 |
1800 |
1990 |
| 10" |
1900 |
2200 |
2450 |
| 12" |
2800 |
3175 |
3600 |
| 14" |
3800 |
4300 |
4800 |
Chart 2
Static Pressure based on 100' ofPipe. |
| Diameter |
3500 FPM |
4000 FPM |
4500 FPM |
| 3" |
7.5 |
10.0 |
12.0 |
| 4" |
5.5 |
7.0 |
8.5 |
| 5" |
4.2 |
5.5 |
6.5 |
| 6" |
3.5 |
4.5 |
5.5 |
| 7" |
2.8 |
3.8 |
4.5 |
| 8" |
2.4 |
3.2 |
3.8 |
| 9" |
2.0 |
2.8 |
3.4 |
| 10" |
1.8 |
2.4 |
3.0 |
| 12" |
1.2 |
2.0 |
2.5 |
| 14" |
1.3 |
1.6 |
2.0 |
|
Elbow to Straight Pipe Conversion |
| Diameter |
90o
Elbow 1.5 Diameter. Rad. |
Elbow 45o
1.5 Diameter. Rad. |
| 3" |
5' |
2.5' |
| 3" |
6' |
3' |
| 3" |
9' |
4.5' |
| 3" |
12' |
6' |
| 3" |
13' |
6.5' |
| 3" |
15' |
7.5' |
| 3" |
17.5' |
8.75' |
| 3" |
20' |
10' |
| 3" |
25' |
12.5' |
| 3" |
30' |
15' |
Static pressure
of two 4” branches (350 CFM each) and one 5” branch (550 CFM) pulling vacuum
simultaneously = Total 1,250CFM.
|
|
|