|
1. Call us (800.367.3828) and
we will mail you our
Air Handling Design Guide or click here to download a copy.
. Click here for For Tips on Installing Your Air Handling System.
. (you will need Adobe Acrobat) Click here to get Adobe Acrobat.
Take off list for Quotes.
Download this form to ease the process of quoting. Simply fill in quantities needed and fax it over to us at 800-438-7135.
CFM Requirements and Proper Branch Diameter Sizes.
Download this guide to view proper CFM requirements and branch diameter sizes.
2.
Follow these written directions:
 Before you start designing your Air Handling
System you need a floor plan of your shop area including the following:
- Location of dust producing machines: indicate size
& location of dust pick ups on each machine.
- Desired location of dust collector unit.
- Floor to joist measurement.
- Any obstructions that would interfere with the run
of the duct.

You should familiarize yourself with these terms:
 |
CFM - Air Volume in cubic feet per minute. |
 |
FPM - Velocity of Air in feet per minute. |
 |
SP - Static Pressure. This is expressed in
inches water gauge. It is resistance to air at rest in a duct, and is also commonly called
"resistance", "friction", "friction loss", or "pressure
loss." |
 |
VP - Velocity Pressure: expressed in inches
water gauge. It is kinetic pressure in the direction of flow necessary to cause air at
rest to flow at a given velocity. |
It is best to do the following calculations before
you purchase your Dust Collector or the necessary ductwork.
A) Duct Velocity (FPM)
B) Proper Size of Duct
C) Total CFM required D) System Resistance (SP)
A) Duct Velocity
Use the chart below to determine the velocity of your system.
| Type of Dust |
Velocity in Branches |
Velocity in Main |
| Metalworking Dust |
4500 FPM |
4000 FPM |
| Woodworking Dust |
4000 FPM |
3500 FPM |
| Other Light Dust |
4000 FPM |
3500 FPM |
B) Determine the size of each
branch
There are several ways to determine the diameter of the branches.
1. If the machine has a factory installed collar, the manufacturer has determined that the
machine needs that size branch under normal circumstances.
2. If the machine has a metric diameter outlet, convert it into inches, and round off to
the nearest inch. When writing up your parts list you may need to order a custom reducer.
3. If the outlet is rectangular you need to determine the equivalent round diameter. When
you write up your list use a transition.
4. If the branch is smaller than 3" diameter plan using a reducer near the machinery
to increase the branch to 3". Figure the CFM for 3 "(195 CFM).
Determine CFM requirements for each branch. Under the proper velocity note the
CFM of each branch. If working with wood dust, use 4000 FPM in branches ( see above - A)
Duct Velocity ).
C)
Determine Diameter of Main Duct
1. Determine which machines are your primary machines. A primary machine is the machine(s)
that will operate at the same time under the worst conditions. (If you normally operate
two machines, but once a week need to operate a third machine at the same time, then you
must size your system for all three machines.) We generally highlight the primary machines
on the drawing.
2. Sizing the Main Trunk Line. When sizing the main truck line start with the primary
machine farthest from the duct collector. Run that size duct until the next primary branch
enters the main. Increase the main size at that junction to accommodate the CFM total of
the two primaries. You will follow this practice all the way to the collector, sizing all
primary junctions, to accommodate total CFM of all primaries at that point. Do not
increase main duct size when a branch other than a primary enters. Your total
CFM
requirement is the total of all primary branches. When not using a primary machine you
will close blastgate and divert suction to a secondary machine.
Example: You have 3 primary machines. You have already assigned the branch diameter and
CFM requirements.
| Table Saw, Lathe |
4" Diameter |
350 CFM |
| Radial Saw |
5" Diameter |
550 CFM |
|
A 4” branch will be run from the Table
Saw until it joins with the 4” branch from the Lathe. At this point your main
starts and you need to increase the pipe to handle the combined CFM (350+350 =
700). Using the CFM Chart 1 look up 700 CFM under the appropriate velocity (3500
FPM in the main for wood dust), then look at the corresponding diameter (6").
Run 6" pipe in the main from the Lathe until the branch of the Radial Saw joins
the main.
Here again you need to increase your
main to handle the total CFM (700+550=1250 CFM). Using the chart again you will
see that 1250 CFM is slightly more than volume for 8” diameter. Drop back to 8”
diameter so as not to go below transport velocity. Run the 8" duct in your main
from the Radial Saw to your Dust Collector.
If you are installing an indoor re-circulating dust collector you need not calculate any
more duct diameters. If you are attaching ductwork to the exhaust side of your duct
collector it is accepted practice to use a duct diameter two diameters larger on the
exhaust side than on the inlet side, thus minimizing exhaust and duct resistance.
Chart 1
CFM requirements for
diameter at specified velocity.
Chart 2
Static Pressure based on 100' ofPipe.
Chart 3
Elbow to Straight Pipe Conversion
D) Figure System Resistance (SP)
The total static pressure is several factors added together. They are entry loss, dirty
filter loss, static pressure of the worst branch duct, static pressure of the main duct,
and static pressure of the return duct.
1. There are more complicated ways to figure the entry loss of your system, but we find it
usually equals a loss of 1" water gauge. (Use 1" as a constant.)
2. If your system has filters, add in 2" loss. (If you do not have filters
add zero).
3. The Worst Branch, is the branch with the greatest resistance. The branch with the
greatest resistance is usually a smaller diameter with the most lineal footage of pipe
elbows. Static pressure of worst branch and main duct can be calculated by using the
following Chart 2. Chart 2 is based on 100 feet
of pipe; therefore, you have to convert all elbows to an equivalent of pipe. To convert 90o
and 45o elbows to equivalent feet of pipe use Elbow to Straight
Pipe Conversion chart (see
chart, click here). When figuring the feet of pipe count lateral type branches
as 45o elbows. Flexhose has a lot of resistance depending on the amount of bends
included in the installation. For this reason we suggest you keep hose to a minimum.
Multiply your length of flexhose on your worst branch by 3 for equivalent length
of straight pipe.
|
Example: Determine Static
Pressure of Worst Branch
Static Pressure (Inches of Water Gauge) in
Worst Branch (4" Table Saw) |
|
Description - 4"
Diameter.......................Equivalent to Straight Pipe.
Straight Pipe.................................................................20'
2 - 90o
elbows...............................................................12'
2 - 45o
elbows.................................................................6'
5' flexhose (3x)..............................................................15'
--------------------------------------------------------------------------------------
Total
equivalent straight pipe after conversions ...............53' |
|
Example: Static Pressure in
MAIN DUCT 6" and 8”
The static pressure of the Main Duct is done
the same way, except you figure it out for each diameter in the Main,
starting farthest away and working toward the collector. |
Description - 6"
Diameter...............................Equivalent to Straight Pipe
Straight
Pipe.................................................................20'
--------------------------------------------------------------------------------------
Total equivalent straight pipe after
conversions...............20'
700 CFM in 6" diameter = 3.5"
S.P. per 100'
700 CFM in 6" diameter =
.70" S.P. per 20' |
Description - 8"
Diameter.............................Equivalent to Straight Pipe
Straight
Pipe.................................................................25'
2 - 90o
Elbows.............................................................30'
--------------------------------------------------------------------------------------
Total equivalent straight pipe after
conversions.............55'
1,250 CFM in 8" diameter = 2.4" S.P. per 100'
1,250 CFM in 8" diameter = 1.3" S.P. per
55'
(8" Diameter runs to self contained Dust
Collector) |
|
Total Static Pressure 1" + 2"
+ 3.71" + .70" + 1.3" = 8.71" S.P. Inches Water Gauge! |
3. If clean air return duct is required, duct resistance should also be
calculated. Now you have all the information you need to make an educated
decision in purchasing your dust collector. You have determined the Velocity,
CFM, Static Pressure and the size of the ductwork. To develop your list of
materials required, go through the system; this time starting at the dust
collector and list each part you will need. Don't forget the assembly equipment
such as: pop rivets, hangers, strapping, caulking, and couplings. To order
please call: (800) 367-3828; fax: (800) 438-7135; or order on-line at
www.airhand.com. If you have any questions while you are designing your system
give us a call.
For additional information on designing your Air
Handling System, we recommend reading Woodshop Dust
Control, by professional woodworker Sandor Nagyszalanczy. Sandor provides
practical, shop-tested solutions to total dust control so you can build the
right system without complex calculations.
BACK TO TOP
|